WNS horizontal internal combustion gas-fired boiler
Fuel type: natural gas
Typical application: garment factories, laundries, food manufacturers, power plants, district heating, schools, hospitals, heating and industrial steam and hot water supply etc.
Thermal efficiency: ≥100%
Boiler capacity: 1 – 10t/h
The WNS horizontal internal combustion three-pass full wet-back boiler is fitted with a fully corrugated furnace, which increases the heat transfer area and bolsters stability. It is constructed using the full flange butt welding technique reducing thermal stress of the furnace. The tubes are welded to the tube plates using the ‘expand first, then weld’ technique, which eliminates corrosion problems and prolongs the lifespan of the boiler. The smoke tubes come with helical internal ribs which improve the heat exchange coefficient of the boiler. The WNS series are highly thermal efficient with low fuel consumptions. They have a high degree of automation, stable outputs, and are easy to maintain. The installation is relatively simple and less time consuming.
FEATURES
Complete combustion system
100% corrugated furnace with large combustion chamber
Advanced engineering
Thermal efficiency ≥92%
Dual fuel design
Automatic control system
Low carbon footprint and eco-friendly
Compliant with national manufacturing specifications
Investment cost
Abundant fuel sources with stable prices
Automatic feeding system minimising human intervention
Only requires one operator
SPECIFICATION
Model | ||||||||||||||
WNS0.5-0.7-Y、Q-| | WNS1-1.0-Y/Q | WNS2-1.25-Y/Q | WNS3-1.25-Y/Q | WNS4-1.25-Y/Q | WNS6-1.25-Y/Q | WNS8-1.25-Y/Q | WNS10-1.25-Y/Q | WNS12-1.25-Y/Q | WNS15-1.25-Y/Q | WNS20-1.25-Y/Q | ||||
Speficiation | Rated evaporation | t/h | 0.5 | 1 | 2 | 3 | 4 | 6 | 8 | 10 | 12 | 15 | 20 | |
Rated steam pressure | Mpa | 0.7 | 1.0 | 1.25/1.6 | ||||||||||
Rated steam temperature | ℃ | 170 | 184 | 193.3/204 | ||||||||||
Design exhaust temperature | ℃ | 150 | ||||||||||||
Boiler full water volume | L | 1350 | 2832 | 4520 | 6900 | 7300 | 7677 | 12700 | 17400 | 29500 | 37049 | 42500 | ||
Design thermal efficiency | % | ≥92 | ||||||||||||
Heated surface | Ontology | m2 | 15.5 | 24.5 | 50.6 | 82.9 | 100.7 | 162.31 | 209.26 | 252.4 | 354 | 364.1 | 493 | |
Economizer(Atmospheric) | m2 | / | 12.9 | 21 | 27 | 41.5 | / | |||||||
Steel economizer(Pressure) | m2 | / | 32 | 43 | 54 | 65 | 81 | 108 | ||||||
Fuel consumption | Natural gas | Nm³/h | 40.94 | 78.87 | 158.37 | 237.51 | 316.68 | 411.16 | 559.6 | 699.5 | 803.4 | 1004.25 | 1339 | |
Pipe | Main steam valve diameter | DN | 40 | 50 | 80 | 100 | 125 | 150 | 200 | 225 | ||||
Water inlet diameter | DN | 25 | 32 | 40 | 50 | 80 | 65 | |||||||
Safety valve diameter | mm | 40 | 50 | 65 | 50*2 | 65*2 | 80*2 | 100*2 | ||||||
Blowoff valve diameter | DN | 40 | 50 | 50*2 | 65*2 | |||||||||
Chimney | Φ | 280 | 300 | 350 | 400 | 450 | 500 | 600 | 700 | 800 | 900 | 1000 | ||
Overall size | Weight | t | 2.8 | 4.6 | 7.6 | 11.2 | 12.5 | 17.6 | 21 | 25 | 37 | 39 | 48 | |
Length | mm | 3464 | 3840 | 4620 | 5126 | 5840 | 6334 | 6894 | 7816 | 8355 | 8379 | 9230 | ||
Width | mm | 1600 | 1760 | 1980 | 2300 | 2432 | 3062 | 2766 | 3250 | 3636 | 3650 | |||
Height | mm | 1790 | 2064 | 2367 | 2718 | 2872 | 3368 | 3468 | 3840 | 3707 | 4250 | |||
Pump | Model | QDL2-11 | QDL2-16 | QDL4-18 | QDL4-20 | QDL8-19 | QDL8-20 | QDL12.5-11 | QDL12.5-13 | QDL18-12 | QDL18-13 | DLG-G36*6 | ||
Input power | Kw | 1.4 | 3 | 4 | 7.5 | 11 | 15 | 18.5 | 22 | 30 |